2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule
2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule 11 min read • Updated

Load-Bearing Door & Window Header Span Table (IRC R602.7)

Size exterior and interior load-bearing headers with 2024 IRC Table R602.7 spans for 2x6 to 2x12 lumber and LVL beams, spacer shims, and jack stud counts.

Published by LayoutCalculator • Formulas reference published code tables; confirm with your local building official.
Companion 2D SVG CAD Instrument

Need an Instant Scale Blueprint? Launch Header Size Calculator

Generate real-time 1/16" fractional dimensions, framing square marks, and printable workshop sheets.

Open the Header Size Calculator →
Direct Code Summary • 2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule SPEC BULLETIN

What Is the Standard Rule for Load-Bearing Door & Window Header Span Table (IRC R602.7)?

2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule: Under 2024 IRC Table R602.7(1) (28-ft wide house, 30 psf snow), a 2-2x10 header spans about 6'-5" supporting roof + ceiling only, dropping to about 5'-4" when it also carries one center-bearing floor (values interpolated between the 24 ft and 36 ft columns). Flush out a double 2x header (3.00" combined wood) inside a 2x4 wall (3.50" actual) with a 1/2" CDX plywood or OSB center shim; in 2x6 walls, add 2.5" rigid XPS foam on the warm side.

LIVE FIELD SOLVER

Interactive Jobsite Verification Instrument

2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule
Instant Field Calculation
25 Studs + 9 Plates (10% Waste)
Adjust inputs above for live takeoff

Key Engineering & Code Takeaways

  • Under 2024 IRC Table R602.7(1) (28-ft wide house, 30 psf snow), a 2-2x10 header spans about 6'-5" supporting roof + ceiling only, dropping to about 5'-4" when it also carries one center-bearing floor (values interpolated between the 24 ft and 36 ft columns).
  • Flush out a double 2x header (3.00" combined wood) inside a 2x4 wall (3.50" actual) with a 1/2" CDX plywood or OSB center shim; in 2x6 walls, add 2.5" rigid XPS foam on the warm side.
  • IRC Table R602.7(1) specifies exact minimum jack (trimmer) studs per end—jumping from 1 jack per side on narrow 3-ft doors to 2 or 3 jacks per side on wide sliders and garage headers.
  • In non-load-bearing interior partition walls (IRC R602.7.4), heavy built-up 2x10 headers are unnecessary—a single flat 2x4 or 2x6 head piece with cripples carries drywall cleanly up to 8 feet.

This is the main reference for the header size calculator topic. Go deeper with

2024 IRC Table R602.7(1) Exterior Bearing Header Spans (No. 2 Lumber, 28-Ft Building Width Interpolated, 30 psf Snow; 2-Story = One Center-Bearing Floor)

← Swipe table horizontally → 2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule
2024 IRC Table R602.7(1) Exterior Bearing Header Spans (No. 2 Lumber, 28-Ft Building Width Interpolated, 30 psf Snow; 2-Story = One Center-Bearing Floor) (2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule)
Header AssemblyRoof + Ceiling Only (1-Story)Jacks / End (1-Story)Roof + 1 Floor Above (2-Story)Jacks / End (2-Story)
2 - 2x6 4'-4" Max Span 1 Jack Stud 3'-7" Max Span 2 Jack Studs
2 - 2x8 5'-5" Max Span 2 Jack Studs 4'-7" Max Span 2 Jack Studs
2 - 2x10 6'-5" Max Span 2 Jack Studs 5'-4" Max Span 2 Jack Studs
2 - 2x12 7'-8" Max Span 2 Jack Studs 6'-4" Max Span 2 Jack Studs
3 - 2x8 6'-10" Max Span 1 Jack Stud 5'-8" Max Span 2 Jack Studs
3 - 2x10 8'-1" Max Span 2 Jack Studs 6'-9" Max Span 2 Jack Studs
3 - 2x12 9'-6" Max Span 2 Jack Studs 8'-0" Max Span 2 Jack Studs
LVL / engineered headers Per manufacturer span table Per manufacturer Per manufacturer span table Per manufacturer

1. How IRC Table R602.7(1) & (2) Calculate Header Loads

Cutting a new 6-foot patio slider or 8-foot pass-through opening into a load-bearing wall transfers every roof rafter, ceiling joist, and upper-story floor joist above that gap onto two vertical jack (trimmer) studs at the ends of a horizontal beam called a header. Under 2024 IRC Section R602.7, required header depth is governed by three inputs: ground snow load (30 psf, 50 psf, or 70 psf), total building width (tabulated at 12 ft, 24 ft and 36 ft measured perpendicular to the ridge, with interpolation permitted between them), and number of stories above (Roof & Ceiling Only on a ranch or second floor vs. Roof, Ceiling & 1 Center-Bearing Floor on the first story of a two-story house).

Notice in the table above how adding a second-story floor slashes a 2-2x10 header span from 7'-3" down to 5'-3"! Equally critical is the Required Number of Jack Studs (NJ) column right inside IRC Table R602.7(1). Even if a header beam itself is strong enough not to bend, bearing 6,000 lbs onto a single 1-1/2" × 3-1/2" (5.25 sq in) jack stud crushes the horizontal bottom plate fibers perpendicular to the grain (F_c⊥ typically 425–625 psi in NDS). Plan your king and double/triple jack stud counts automatically in our Wall Stud & Rough Opening Framing Calculator.

2. Worked Remodel Example: Installing an 8-Foot Bi-Fold Patio Door in a 2-Story Exterior Wall

Suppose a homeowner removes two narrow windows on the first floor of a 28-foot wide, two-story colonial (30 psf snow zone, 2x6 exterior wall, 8-ft ceiling with 92-5/8" king studs) to install an 8'-0" (96") rough-opening patio door:

  • Step 1 (Check Sawn Lumber Limits): Under 2024 IRC Table R602.7(1) (roof, ceiling and one center-bearing floor, 28-ft width interpolated), 2-2x12 stops at about 6'-4", while 3-2x12 reaches about 8'-0" (96")—exactly the opening, with no margin.
  • Step 2 (Decide: 3-2x12 or Engineered Header): A 3-2x12 header (4-1/2" wide) technically meets the table with two jack studs per end. Many builders step up to an LVL or other engineered header instead and size it from the manufacturer's published span table, because a zero-margin sawn header leaves no room for a slightly wider rough opening.
  • Step 3 (Jack & King Studs): Table R602.7(1) lists two jack studs at each end for the 3-2x12 option; for an engineered header follow the manufacturer's required bearing length. Add king studs per Table R602.7.5 and carry the jack-stud load down through solid blocking to the foundation or girder below.
  • Step 4 (Insulate the Remaining 2-Inch Cavity): In a 2x6 (5.50") wall, push the 3.50" 2-ply LVL flush against the exterior OSB sheathing and fill the 2.00" interior pocket with 2-inch foil-faced polyiso (R-13) or XPS (R-10) rigid foam so drywall screws reach the wood edges while stopping cold header condensation.

3. Spacer Shims, Single-Ply Insulated Headers & Non-Bearing Walls

When building conventional 2-ply dimensional headers for a 2x4 (3-1/2" actual) load-bearing wall, two 1-1/2" boards measure only 3.00 inches thick—1/2 inch narrower than the wall plates! Rip 1/2-inch (15/32" CDX plywood or 7/16" OSB plus construction adhesive) filler strips and sandwich them between the two 2x members, crowning both header boards upward before nailing a 16" OC grid from each face (IRC Table R602.3(1)). Two 1-3/4" LVL plies, conveniently, equal 3.50 inches exact with zero plywood ripping!

Under 2024 IRC Table R602.7(3) (Optimal Value Engineering / Advanced Framing), single-ply 2x8, 2x10, or 2x12 headers are also legal over modest 3-ft to 4-ft exterior windows on one-story buildings, leaving 4 full inches inside a 2x6 wall for R-20 insulation (see our California 3-Stud Corner & Advanced Framing Guide). And before over-framing interior closet doors, check joist direction above: on non-load-bearing partitions (IRC R602.7.4) parallel to joists, a flat single 2x4 header spans up to 8 feet effortlessly!

Primary Standards & Building Code Authorities (2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule)

All dimensions, tolerances, and safety thresholds in this field guide are cross-referenced against current US residential building, electrical, and trade standards:

  • ICC International Residential Code (IRC R311.7) Stairway rise/run geometry, headroom, and handrail code requirements. ICC Digital Codes →
  • NFPA 70 / National Electrical Code (NEC 690) Photovoltaic Voc temperature coefficients, ampacity, and OCPD sizing. NFPA Standards →
  • TCNA Handbook & ANSI A108.02 Ceramic and porcelain tile centering, lippage, and EJ171 expansion joints. TCNA Council →
  • APA Engineered Wood & AWC NDS Structural wood panel sizing, kerf allowances, and framing lumber spans. APA Wood →

Pre-Calculated Blueprints for Header Size Calculator (0 Specs)

Related Calculators & Framing & Stairs Hub

Header Size Calculator
2024 IRC Section R602.7
Stair Stringer Calculator
2024 IRC Section R311.7
Roof Rafter Calculator
2024 IRC Section R802
Deck Baluster Calculator
2024 IRC Section R312.1.3
Stud Wall Framing Calculator
2024 IRC Section R602.3
Deck Beam Span Calculator
2024 IRC Section R507
Floor Joist Span Calculator
2024 IRC Section R502.3
Rafter Span Calculator
2024 IRC Section R802.4
Ceiling Joist Span Calculator
2024 IRC Section R802.5
Roof Pitch Calculator
Trigonometry (rise/run)

Frequently Asked Questions: 2024 IRC Tables R602.7(1), R602.7(2) & R602.7.5 Jack Stud Schedule

Can I use metal header hangers instead of jack studs when framing space is tight?

▼

Yes! IRC Section R602.7.1 explicitly permits approved structural header hangers (such as Simpson Strong-Tie HH4 or HH6) fastened directly to full-length king studs to replace 1 or 2 jack studs on cramped corners where door casing trim has minimal clearance.

How do I tell whether an existing interior wall is load-bearing before cutting a wider doorway?

▼

Inspect both the attic above and the basement or crawlspace below: if ceiling joists, roof purlin struts, or second-floor joists run perpendicular to the wall and lap or splice over it—or if a steel I-beam, wood girder, or masonry foundation wall sits directly underneath—treat the wall as load-bearing and shore both sides with temporary stud walls before demo.

Are gable-end exterior walls subject to the same heavy header table as eave walls?

▼

No—when roof rafters or trusses run parallel to an exterior gable-end wall and transfer zero roof load onto it, 2024 IRC Table R602.7(3) allows lighter gable-end header spans because the wall only supports its own rake framing and siding above.