How to Read the IRC Header Span Table
IRC Table R602.7(1) sizes headers and girders in exterior bearing walls by what they carry (roof and ceiling, plus one or two floors), the ground snow load, and the building width measured perpendicular to the ridge. Each cell gives the maximum span and the number of jack studs required at each end.
For a 24 ft wide house with 30 psf or less ground snow, a header carrying only the roof and ceiling can be 2-2x10 up to 6 ft 10 in with two jack studs per end, or 2-2x12 up to 8 ft 1 in. Widths between 12, 24 and 36 ft may be interpolated.
The spans assume the top of the header is braced by perpendicular framing. When cripple studs bear on the header instead, footnote f reduces 2x8, 2x10 and 2x12 header spans to 70%. Interior bearing-wall headers use Table R602.7(2).
Header Span Chart: Exterior Wall Supporting Roof & Ceiling Only
| Header | 12 ft wide | 24 ft wide | 36 ft wide |
|---|---|---|---|
| 2-ply 2x4 | 4'-0" (1J) | 3'-1" (1J) | 2'-7" (1J) |
| 2-ply 2x6 | 6'-0" (1J) | 4'-7" (1J) | 3'-10" (1J) |
| 2-ply 2x8 | 7'-7" (1J) | 5'-9" (1J) | 4'-10" (2J) |
| 2-ply 2x10 | 9'-0" (1J) | 6'-10" (2J) | 5'-9" (2J) |
| 2-ply 2x12 | 10'-7" (2J) | 8'-1" (2J) | 6'-10" (2J) |
| 3-ply 2x8 | 9'-5" (1J) | 7'-3" (1J) | 6'-1" (1J) |
| 3-ply 2x10 | 11'-3" (1J) | 8'-7" (1J) | 7'-3" (2J) |
| 3-ply 2x12 | 13'-2" (1J) | 10'-1" (2J) | 8'-6" (2J) |
| 4-ply 2x8 | 10'-11" (1J) | 8'-4" (1J) | 7'-0" (1J) |
| 4-ply 2x10 | 12'-11" (1J) | 9'-11" (1J) | 8'-4" (1J) |
| 4-ply 2x12 | 15'-3" (1J) | 11'-8" (1J) | 9'-10" (2J) |
| 1-ply 2x6 | 4'-0" (1J) | 3'-1" (2J) | 2'-7" (2J) |
| 1-ply 2x8 | 5'-1" (2J) | 3'-11" (2J) | 3'-3" (2J) |
| 1-ply 2x10 | 6'-0" (2J) | 4'-8" (2J) | 3'-11" (2J) |
| 1-ply 2x12 | 7'-1" (2J) | 5'-5" (2J) | 4'-7" (3J) |
Source: 2024 IRC Table R602.7(1), 30 psf ground snow. Values transcribed from the published table; confirm local amendments with your building department.