NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122 10 min read • Updated

Solar Panel Frame Bonding & EGC Wire Sizing (NEC 690.43)

Size solar equipment grounding conductors per NEC 690.43 and Table 250.122: WEEB rail washers, 6 AWG bare copper vs 10 AWG in conduit.

Published by LayoutCalculator • Formulas reference published code tables; confirm with your local building official.
Companion 2D SVG CAD Instrument

Need an Instant Scale Blueprint? Launch Solar Wiring & NEC Calculator

Generate real-time 1/16" fractional dimensions, framing square marks, and printable workshop sheets.

Open the Solar Wiring & NEC Calculator →
Direct Code Summary • NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122 SPEC BULLETIN

What Is the Standard Rule for Solar Panel Frame Bonding & EGC Wire Sizing (NEC 690.43)?

NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122: Clear and black anodized aluminum solar module frames and racking rails are coated in non-conductive aluminum oxide; standard flat bolts do NOT create a legal electrical bond! Use UL 2703 Listed bonding mid-clamps (IronRidge UFO, Unirac) or stainless-steel WEEB serrated piercing washers so removing one solar panel for service never interrupts bonding of remaining modules (NEC 690.43(C)).

LIVE FIELD SOLVER

Interactive Jobsite Verification Instrument

NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122
Instant Field Calculation
8 AWG Copper (1.14V Drop)
Adjust inputs above for live takeoff

Key Engineering & Code Takeaways

  • Clear and black anodized aluminum solar module frames and racking rails are coated in non-conductive aluminum oxide; standard flat bolts do NOT create a legal electrical bond!
  • Use UL 2703 Listed bonding mid-clamps (IronRidge UFO, Unirac) or stainless-steel WEEB serrated piercing washers so removing one solar panel for service never interrupts bonding of remaining modules (NEC 690.43(C)).
  • Per NEC 690.45 and Table 250.122, a 10 AWG copper Equipment Grounding Conductor (EGC) pulled inside conduit protects PV circuits up to 60A, whereas exposed bare copper on roof rails subject to damage requires 6 AWG (NEC 250.120(C)).
  • NEVER drive a standalone unbonded ground rod at a ground-mount or inverter without tying it to the main house Grounding Electrode System with 6 AWG copper (NEC 250.50), or nearby lightning strikes will flash across your MPPT!

Part of our Solar & Electrical series; start with NEC 690.7 Cold Weather Solar Voc Formula & MPPT Sizing. Related: EMT & PVC Conduit Fill Chart for 10 AWG PV Wire (NEC 9), LiFePO4 Voltage Chart, RV DC-to-DC Alternator Charger + Solar MPPT Wiring Guide.

NEC 690.45 & Table 250.122 Solar Equipment Grounding Conductor (EGC) Sizing & Bonding Reference

← Swipe table horizontally → NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122
NEC 690.45 & Table 250.122 Solar Equipment Grounding Conductor (EGC) Sizing & Bonding Reference (NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122)
PV Circuit OCPD / CaseMin Copper EGC (In Conduit)Exposed Rooftop Bare CuAluminum Rail Bonding HardwareApplicable NEC Rule
15A to 20A Single String 12 AWG Cu (10 AWG std) 6 AWG Bare Solid Cu UL 2703 Mid-Clamp + Rail Lug NEC 690.45 & 250.122
25A to 60A PV Sub-Array 10 AWG Green/Bare Cu 6 AWG Bare Solid Cu Tin-Plated Lay-In Lug (No Cu-on-Al!) NEC 250.122 & 110.14
70A to 100A Combiner Run 8 AWG Green/Bare Cu 6 AWG Bare Solid Cu UL 2703 Splice Bar Bonding Clip NEC Table 250.122
110A to 200A Commercial PV 6 AWG Green/Bare Cu 6 AWG Bare Solid Cu Listed Rail-to-Rail Jumper NEC Table 250.122
Unprotected Exposed EGC N/A (Outside Raceway) 6 AWG Min (Physical Dmg) Stainless 1/4-20 Flange + Star NEC 250.120(C) & 690.46
Ground-Mount Aux Electrode Bond to House GES (6 AWG) 8-ft Copper-Clad Rod Acorn Clamp at Array Post (Optional) NEC 250.50 & 250.54

1. Piercing Anodized Aluminum: UL 2703 Racking Clamps, WEEB Clips & Galvanic Corrosion

If you place a digital multimeter set to continuity (Ω) across the black or silver anodized surface of a brand-new solar panel frame, it reads Open Circuit (OL / Infinite Ohms)! Anodizing intentionally grows a tough ceramic aluminum-oxide (Al2O3) insulating skin to stop weather corrosion. Bolting solar panels onto aluminum Unistrut or racking rails with ordinary smooth stainless bolts leaves every 40-lb metal frame electrically floating—meaning if a chafed 400V DC string wire touches a panel edge, it energizes the frame waiting to shock anyone cleaning leaves off the roof!

Under NEC Section 690.43, modern UL 2703 Listed racking systems (such as IronRidge, Unirac, SnapNRack, and Tamarack) embed sharp stainless-steel teeth directly into every T-bolt mid-clamp and rail splice so tightening the single clamp nut pierces the anodization of both adjacent panels and bonds them into the rail simultaneously—satisfying NEC 690.43(C) so unbolting one broken panel never breaks ground continuity for neighboring panels. On custom DIY Unistrut or RV Z-bracket mounts, slip a listed stainless Wiley WEEB piercing washer between each frame flange and rail, and land your copper ground wire ONLY onto a tin-plated aluminum/copper lay-in lug (direct bare copper clamped onto raw aluminum corrodes electrolytically in rain!). Size your array currents and OCPD ratings first in our Solar Panel Series-Parallel & NEC Calculator.

2. Sizing the Equipment Grounding Conductor (EGC): 6 AWG Bare on Roof vs 10 AWG in Conduit

Inspectors evaluate your solar Equipment Grounding Conductor under two separate NEC rules—electrical fault ampacity (NEC 690.45 / Table 250.122) and mechanical abuse protection (NEC 250.120(C) & 690.46):

  • Exposed Along Roof Rails (Outside Conduit): Because exposed rooftop ground wires endure ice sliding, wind vibration, squirrels, and boot steps during installation, most AHJs enforce NEC 250.120(C): an EGC smaller than 6 AWG that is exposed to physical damage must be enclosed in raceway—making 6 AWG bare solid copper clipped cleanly along the racking rail up to the roof junction box the universal zero-headache standard!
  • Inside Roof Junction Box & EMT / PVC Conduit: Once you enter a weatherproof roof transition box (e.g., SolaDeck or EZ Solar JB) and transition into EMT or Schedule 80 PVC conduit heading down to your combiner or inverter, the wire is mechanically protected! Inside conduit, Table 250.122 allows stepping down to 10 AWG green THWN-2 or bare copper for any PV circuit protected up to 60 Amps (recall that if you upsize current-carrying PV wires for long-distance voltage drop, NEC 250.122(B) requires upsizing the EGC proportionally in circular mils!).

3. Equipment Bonding vs Functional Grounding — And the Deadly Isolated Ground Rod Myth

Never confuse Equipment Grounding (EGC — green/bare safety wire tied to metal frames and chassis) with DC System Grounding (tying PV- or Battery- to earth)! Virtually 100% of modern transformerless grid-tied inverters, all-in-one hybrid inverters, and off-grid MPPT controllers use functionally ungrounded (floating) PV inputs monitored continuously by internal Ground-Fault Detection and Interruption (GFDI) circuitry per NEC 690.41(B). Intentionally jumpering PV Negative to your ground busbar shorts out the internal GFDI sensor and triggers an immediate Inverter Fault shutdown!

Even more dangerous is the internet myth of driving a standalone "dedicated solar ground rod" out at a backyard ground mount without connecting it back to the house main panel ground rod! Soil has high resistance (15 to 100+ Ohms). If lightning strikes a tree 200 feet away, a 5,000-Volt potential gradient develops across the yard between the isolated solar rod and the house utility rod—sending a lethal surge straight through your MPPT controller’s circuit board! Under NEC 250.50 and 250.54, run an unbroken EGC inside the PVC trench alongside your PV wires back to the main building Grounding Electrode System; if you also drive an optional auxiliary ground rod at the steel ground-mount rack (NEC 250.54), it connects only to the local equipment ground frame while the trench EGC ties the two systems together.

Primary Standards & Building Code Authorities (NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122)

All dimensions, tolerances, and safety thresholds in this field guide are cross-referenced against current US residential building, electrical, and trade standards:

  • ICC International Residential Code (IRC R311.7) Stairway rise/run geometry, headroom, and handrail code requirements. ICC Digital Codes →
  • NFPA 70 / National Electrical Code (NEC 690) Photovoltaic Voc temperature coefficients, ampacity, and OCPD sizing. NFPA Standards →
  • TCNA Handbook & ANSI A108.02 Ceramic and porcelain tile centering, lippage, and EJ171 expansion joints. TCNA Council →
  • APA Engineered Wood & AWC NDS Structural wood panel sizing, kerf allowances, and framing lumber spans. APA Wood →

Pre-Calculated Blueprints for Solar Wiring & NEC Calculator (12 Specs)

Related Calculators & Solar & Electrical Hub

Solar Wiring & NEC Calculator
NFPA 70 / NEC Article 690 (2023/2026)

Frequently Asked Questions: NFPA 70 (2023/2026 NEC) Sections 690.43, 690.45 & 250.122

Does metallic EMT conduit count as an Equipment Grounding Conductor by itself without pulling a green wire?

▼

While NEC 250.118 technically recognizes properly listed EMT fittings as an equipment grounding path indoors, solar rooftop thermal expansion (-20°F to +150°F) loosens set-screw couplings over time, and many solar inverter manufacturers and AHJs explicitly require a dedicated insulated green or bare copper EGC pulled inside every PV conduit run (plus grounding bushings on concentric/eccentric knockouts above 250V to ground per NEC 250.97!). Always pull a copper EGC wire.

Do camper van and fiberglass boat solar panel frames need grounding?

▼

On metal-bodied camper vans and RVs, there is no earth ground rod—instead, the steel vehicle chassis serves as the common negative/safety reference! For low-voltage (under 50V) rooftop RV panels bolted via anodized brackets onto painted roofs, bonding metal frames with 10 AWG wire and star washers to the vehicle chassis prevents static build-up and ensures the MPPT fuse trips immediately if a positive MC4 lead chafes against a sharp aluminum frame edge.

Can I reuse a tin-plated lay-in lug or WEEB washer if I relocate a solar panel?

▼

No for single-use WEEB piercing washers! WEEB teeth flatten slightly as they bite into aluminum oxide on the first torque cycle (typically 7 to 10 ft-lbs); UL 2703 installation manuals require inserting a fresh unused WEEB clip whenever a module is unbolted and reinstalled.