ACI 318 / IRC R403 Pier Concrete & Foundations

16" Pier + 28" Bell Base — 16" × 42" Flared Bell-Base Pier Concrete Volume

2D CAD concrete footing plan for 16-inch Sonotubes on 28-inch flared bell bases: 6.20 cu ft per pier, 8,553 lbs soil bearing capacity, and bag/yardage.

Calculation notes
Checked against: 2024 IRC R403 & ACI 318
Published by LayoutCalculator. Confirm with your local building official.
REV DATE:
Result summary

Pairing a 16" shaft with a 28" flared bell base expands bearing area to 4.28 sq ft (8,553 lbs allowable load per pier at 2,000 psf). Four piers (+10% waste) total 27.26 cu ft (1.01 cu yd / 46 × 80-lb bags).

Typical Field Application

Heavy timber pergolas, covered porch roofs, two-story deck girders, and uplift-resistant carport columns.

Field note

Molded bell-base funnels double as anti-heave frost anchors—backfill around the flared cone in compacted 8-inch lifts before pouring so wet concrete hydraulic head cannot lift the tube.

IRC R403.1 & ACI 318 2D SVG Concrete Sonotube & Footing Pier Console
80-lb Bags 46 Bags
Volume 1.01 yd³
Pier Load 8,552 lb
16" Ø Tube
8" (Fence) 12" (Deck) 18" (Porch) 36" (Caisson)
42" (3.5 ft)
18" (South) 42" (36" Frost) 54" (48" Frost) 96"
4 Piers
✓ IRC R403.1 FOOTING BEARING VERIFIED 8,552 lb/pier

Each pier supports 8,552 lbs allowable axial load (34,208 lbs across 4 piers). Hand/mixer batch: 46 × 80-lb bags (34.5 gal water).

2D IRC R403.1 Concrete Sonotube Pier, Frost Line, Rebar & Bearing Blueprint Interactive scale CAD cross-section of a cylindrical concrete Sonotube pier showing grade horizon, winter frost line, 6-inch above-grade projection, #4 rebar cage, ABU66Z post standoff base, and soil bearing capacity. FINISH GRADE HORIZON (0.0") WINTER FROST DEPTH LINE (-36") ABU66Z POST BASE + 1/2" J-BOLT (+6" DRY) ↑ ↑ ↑ ALLOWABLE BEARING: 8,552 LBS/PIER @ 2,000 PSF ↑ ↑ ↑ Total: 42" 4 PIERS (16" Ø) | 80-LB BAGS: 46 (1.01 YD³) Single Pier: 6.20 ft³ • Gross w/ 10% Waste: 27.3 ft³
80-lb Mix Bags
46 Bags
Add ~34.5 gal Water
60-lb / 50-lb
61 / 73
60lb / 50lb Bags
Cubic Yards
1.01 yd³
27.3 ft³ Gross
Per-Pier Volume
6.20 ft³
10.3 × 80lb / pier
Max Pier Load
8,552 lb
4.28 ft² Footprint

Concrete Volume, Bag Yield & Bearing Table Bag-Mix Friendly

Calculated per ASTM C387 / Quikrete commercial bag yields (0.60 ft³ per 80-lb bag) and 2024 IRC Table R401.4.1 soil bearing values:

Concrete Sonotube Volume, Bag Counts, Water Ratio, and Soil Bearing Schedule
Engineering Metric Calculated Quantity Jobsite Mix / Code Spec
Single Pier Net Volume 6.20 cu ft 0.229 cu yd net
Gross Batch (+10% Waste) 27.26 cu ft 1.01 cubic yards (4 piers)
80-lb Concrete Bags (0.60 ft³) 46 Bags 1.1 pallets • 34.5 gal mix water
60-lb Concrete Bags (0.45 ft³) 61 Bags 3,660 lbs total dry weight
50-lb Fast-Setting Bags (0.375 ft³) 73 Bags Rapid post/light pier option
Allowable Axial Load / Pier 8,552 lbs 4.28 sq ft @ 2,000 PSF

Required Bill of Materials (BOM) & Hardware

Auto-Calculated Quantities
  • 46 × 80-lb Bags 4,000 PSI Air-Entrained Concrete Mix (or 61 × 60-lb) 1.01 yd³ gross batch including +10% excavation waste
  • 4 × 16" Ø Wax-Lined Cardboard Concrete Pier Forms Plus 4 × 28" Flared Bell Footing Cones (Bigfoot/Redi-Base)
  • 4 × Simpson Strong-Tie ABU66Z Standoff Post Bases & 1/2"×8" HDG J-Bolts Plus 8 × #4 (1/2") Deformed Steel Rebar Dowels (maintain 3" bottom concrete cover)

Independent Field Spec Notice: Footing volumes, soil capacities, and 3-inch earth-cast rebar cover follow 2024 IRC R403.1, Table R401.4.1, and ACI 318. Confirm local winter frost depth with your municipal building department.

Need full-scale Pier Excavation & Batch Sheet + Vector .SVG file?

Pre-Calculated Sonotube Footing Calculator Blueprints (12 Field Specs)

Select any standard jobsite specification below to load its exact 2D SVG diagram and engineering tables:

Open Base Sonotube Footing Calculator →
Contractor & Instructor Widget

Embed This 2D SVG Instrument on Your Website (Ad-Free)

Carpentry instructors, trade schools, and builders can embed the standalone ad-free version of this 2D CAD calculator with one HTML snippet.

SPECIFICATION WALKTHROUGH // 16" Pier + 28" Bell Base

Mathematical Derivation & Field Specifications: 16" Pier + 28" Bell Base

Updated • Published by LayoutCalculator

Pouring 4 concrete footings with a 16" shaft diameter and 42" total depth (paired with a 28" flared bell base) requires 6.20 cu.ft net volume per pier. Including a 10% earth-auger and spillage allowance yields 27.26 cu.ft (1.01 cubic yards) total concrete.

Order 46 bags of 80-lb pre-blended concrete (0.60 cu.ft/bag), 61 bags of 60-lb mix (0.45 cu.ft/bag), or 73 bags of 50-lb mix, hydrated with approximately 34.5 gallons of clean water. Resting on 2,000 PSF soil per 2024 IRC Table R401.4.1, each pier's 4.28 sq.ft footprint supports up to 8,552 lbs.

Tube Diameter Volume & Soil Bearing Comparison (4 Piers @ 42" Depth)

Tube Size Net / Pier Gross Total (+10%) 80-Lb Bags 60-Lb Bags Soil Bearing / Pier
8" Tube 1.22 ft³ 5.38 ft³ 9 Bags 12 Bags 698 lbs
10" Tube 1.91 ft³ 8.40 ft³ 14 Bags 19 Bags 1,091 lbs
12" Tube 2.75 ft³ 12.10 ft³ 21 Bags 27 Bags 1,571 lbs
16" Tube 4.89 ft³ 21.50 ft³ 36 Bags 48 Bags 2,793 lbs
20" Tube 7.64 ft³ 33.60 ft³ 56 Bags 75 Bags 4,363 lbs

Pier Excavation, Rebar Cage & Pour Lift Schedule (42" Total Pier Height)

Elevation Zone Target Dimension ACI 318 / IRC R403 Field Requirement
1. Subgrade Base 36" Below Grade 6"+ below local frost depth on undisturbed native soil
2. Rebar Clear Cover 3" Bottom / 2" Side Suspend #4 vertical bars on plastic chairs (never driven into dirt)
3. Above-Grade Plinth +6" Splash Reveal Wet-set 1/2" or 5/8" HDG J-bolt w/ 7" embedment for Simpson ABU base

Official Building Code & Industry Standard Citations

  • ICC International Residential Code (IRC R403.1) Sets minimum footing sizes by load and presumptive soil bearing capacity, and requires footings to bear below the local frost line. Reference: ICC Digital Codes (codes.iccsafe.org).

Field Manuals & Code Tables for Sonotube Footing Calculator

Index of All 107 Manuals →

Frequently Asked Questions (16" Pier + 28" Bell Base)

How many 80-lb and 60-lb bags of concrete do 4 piers of 16" × 42" require?

▼

Each 16" × 42" flared bell-base (28" bell) pier holds 6.20 cu.ft net. For 4 piers with 10% waste (27.26 cu.ft / 1.01 cu.yd), purchase 46 bags of 80-lb mix (or 61 bags of 60-lb mix) and ~34.5 gallons of clean water.

How much vertical load can one 16" pier with a 28" bell base support at 2000 PSF?

▼

With a bottom bearing footprint of 4.28 sq.ft resting on undisturbed 2,000 PSF soil per IRC Table R401.4.1, each pier supports up to 8,552 lbs of allowable tributary dead-plus-live load.

Should I mix bagged concrete or order a ready-mix truck for 27.3 cu.ft (1.01 yd³)?

▼

At 1.01 cubic yards (46 × 80-lb bags), mixing 4,000 PSI bagged concrete on-site in a 3.5–5.0 cu.ft drum mixer avoids ready-mix short-load delivery fees.